Orifice and Venturi Flow: Reading dP the Right Way

Read flow from differential pressure with a calibrated factor Q = C sqrt(dP/rho), then verify beta, straight runs, and density compensation.

Metering

Differential-pressure meters trade a calibrated restriction for a square-root flow reading. Calibrate the meter factor C from one trusted point, hold beta between 0.2 and 0.75, provide 10-20 diameters of straight run upstream and 5 downstream, and compensate liquid density for temperature. Custody transfer needs the full ISO 5167 treatment with discharge coefficient and expansibility.

Formulas

dP to flow

Q = C x sqrt(dP / rho)

C from calibration; rho at flowing conditions.

Calibration

C = Q / sqrt(dP/rho)

One trusted point fixes C for the run.

Worked example

Water run at 25 kPa

Inputs: C 50; dP 25; rho 1000.

Calculation: Q = 50 x sqrt(0.025) = 7.91 m3/h.

Lesson:

Frequently asked questions

What is C?

Calibrated factor linking dP to flow for one meter run.

How much straight run?

Roughly 10-20D upstream and 5D downstream, plus conditioner if short.

Does density matter?

Yes for liquids; gases need compressibility and expansion corrections.