PID Form Converter

Parallel PID: Ki = Kp/Ti, Kd = Kp Td.

Inputs

Inputs

Result

Kd (x min)
2.000
Ki (per min)
0.400
Td (seconds)
60 s
Ti (seconds)
300 s

About this calculator

What this calculator does

This converter expresses a parallel PID controller using proportional gain Kp, integral time Ti, and derivative time Td. With Ti and Td entered in minutes, it calculates:

PID signal path from setpoint through filtering and split-range valve outputs
Controller tuning, process response, filtering, and split-range mapping act at different points in the loop.

Ki = Kp/Ti in gain per minute, Kd = Kp×Td in gain·minutes, and the equivalent Ti and Td in seconds.

These are parameter conversions within the same parallel-form convention. They are not a universal mapping between every vendor's ideal, series, ISA, velocity, or filtered-derivative form.

Reading the result

At Kp = 2, Ti = 5 min, and Td = 1 min, the outputs are Ki = 0.400 per min, Kd = 2.000 gain·min, Ti = 300 s, and Td = 60 s. The time-unit conversion changes the displayed units; it does not change the physical tuning time.

Changing Ti affects Ki inversely: halving Ti doubles Ki. Changing Td affects Kd directly: doubling Td doubles Kd. Kp scales both derived gains. A zero derivative time is allowed and produces Kd = 0, which represents proportional-integral control without derivative action.

When to use / when not to use

Use this page to check arithmetic when moving parameters between interfaces that explicitly use the same parallel definitions and time units. It does not select stable tuning values, account for output limits, anti-windup, derivative filtering, sample time, controller direction, or process dynamics. Confirm the target controller's exact form and units before applying any converted value to a live loop.

Input and output variables

Kp/Ti/Td
Academic form
Target
ISA standard vs series form
Mapping
Gain and time-constant conversion

Worked example

At Kp=2, Ti=5 min, and Td=1 min, the converter gives Ki=0.400 per min, Kd=2.000 gain-min, Ti=300 s, and Td=60 s.

Standards: Ziegler-Nichols (starting point)

Frequently asked questions

How do I use the PID Form Converter?

Enter entered inputs with units as labeled, read each output with its substituted formula, then verify against datasheets and field readings before acting.

Is this result final?

Starting-point tuning only. Validate on the live loop before commissioning.

Learn

How to interpret the result

Move PID gains between DCS forms.

Checklist before you rely on it

  1. Confirm units match the input labels before trusting the result.
Screening result for preliminary sizing only. Verify against the manufacturer datasheet and applicable standard before procurement or construction.

Related calculators

Workspace

Save this calculation to your workspace

Save this calculation to your private workspace: keep inputs + result, compare scenarios side by side, and export a report with substituted formulas.

  • Save projects — return to inputs, result, and report.
  • Compare scenarios — see which option holds margin.
  • Export report — PDF/CSV with formulas shown.

Sign in or create an account to save this calculation.