Control Valves
Actuator Sizing Margin
Actuator margin = (rated/required - 1) x 100%. Require >= 25%.
Open calculatorCalculator category
Twelve control valve sizing screens that follow the order a specification is actually settled in: required Cv from flow and pressure drop, the Cv the trim delivers at the opening you can use, valve authority inside the loop, and then the limits that cap the result — choked flow, cavitation, noise and actuator margin. Liquid, gas and steam paths each carry their own equation, printed with your numbers substituted, alongside Cv/Kv conversion and steam property tables.
Control Valves
Actuator margin = (rated/required - 1) x 100%. Require >= 25%.
Open calculatorControl Valves
Allowable drop with choked-flow flag.
Open calculatorControl Valves
Regime plus SPL proxy before vendor prediction.
Open calculatorControl Valves
Cv to Kv and Kv to Cv. Kv = 0.865 x Cv.
Open calculatorControl Valves
Gas valve screening with choked-flow flag at P2/P1 <= 0.5. Full sizing per IEC 60534.
Open calculatorControl Valves
Liquid Cv to flow at given dP and specific gravity. Kv = 0.865 x Cv.
Open calculatorControl Valves
Required Cv from target flow, dP and SG, with 20% margin recommendation.
Open calculatorControl Valves
Critical-flow orifice area on API 520 basis.
Open calculatorControl Valves
Saturation pressure and enthalpies from temperature.
Open calculatorControl Valves
Valve dP over system dP.
Open calculatorControl Valves
Opening-to-flow ONLY with manufacturer curve data. Never assume 50% open = 50% flow.
Open calculatorControl Valves
Valve pressure drop from flow and Cv: dP = SG x (Q/Cv)^2.
Open calculator