Why Valve Opening % Is Not Flow % (And What to Enter Instead)

Valve opening % sets stem travel, not flow %. Flow follows the trim characteristic Cv(h) and the pressure drop available at that opening. Estimate flow only with datasheet curve data.

Controlvalves

Linear vs equal-percentage trims

A linear trim adds the same Cv per percent of travel, which suits level loops with constant drop. An equal-percentage trim adds Cv geometrically, which compensates for a system whose available drop shrinks as flow rises. The datasheet rangeability R, typically 25 to 50, fixes the exact curve; without it any opening-to-flow number is a guess.

Why the pressure drop moves with opening

The valve sees only part of the system head. As it closes, line friction falls and the valve takes a larger share of the total drop. That shifting drop is why installed characteristics differ from inherent bench curves, and why flow must be recomputed at each opening instead of scaled.

What you must enter instead of a percentage

Use the rated Cv at full open, the opening fraction h, the valve dP at that opening, and the fluid SG. For equal-percentage trims add R. Control below roughly 10% open is unreliable on most trims, so resize rather than throttle there.

Worked check: 60% open, linear trim

Rated Cv 100 at h = 0.6 gives Cv(h) = 60. At dP 1 bar and SG 1 the flow is 60 x 1.156 x sqrt(1) = 69.36 m3/h. Run the same inputs through the opening estimator to confirm, then size the valve with the required-Cv tool.

Formulas

Opening to flow

Q = 1.156 x Cv(h) x sqrt(dP / SG)

Cv(h) is the trim characteristic at opening h; SG is relative to water.

Equal-percentage trim

Cv(h) = Cv x R^(h-1)

R is datasheet rangeability; h is the 0-1 opening fraction.

Worked example

60% open on a linear trim

Inputs: Cv 100; h 0.6; dP 1 bar; SG 1.

Calculation: Cv(h) = 60. Q = 60 x 1.156 x 1 = 69.36 m3/h.

Lesson:

Frequently asked questions

Can I convert opening % to flow %?

Only with the manufacturer Cv(h) table or rangeability R. Otherwise the result is a guess.

Linear or equal-percentage?

Equal-percentage passes less than linear at the same mid opening; the exact ratio needs R.

Why is control poor below 10% open?

Most trims hunt and cavitate near the seat. Resize or use a smaller trim.