Why Valve Opening % Is Not Flow % (And What to Enter Instead)

Valve opening % sets stem travel, not flow %. Flow follows the trim characteristic Cv(h) and the pressure drop available at that opening. Estimate flow only with datasheet curve data.

Controlvalves

A control valve converts stem travel into flow through its trim characteristic and the pressure drop the system leaves for it. A linear trim delivers Cv(h) = Cv x h; an equal-percentage trim delivers Cv(h) = Cv x R^(h-1) with rangeability R from the datasheet. Because system pressure drop redistributes as the valve strokes, 50% open essentially never means 50% flow. Enter the rated Cv, the opening fraction, the actual valve dP, and SG — or do not estimate at all.

Formulas

Opening to flow

Q = 1.156 x Cv(h) x sqrt(dP / SG)

Cv(h) is the trim characteristic at opening h; SG is relative to water.

Equal-percentage trim

Cv(h) = Cv x R^(h-1)

R is datasheet rangeability; h is the 0-1 opening fraction.

Worked example

60% open on a linear trim

Inputs: Cv 100; h 0.6; dP 1 bar; SG 1.

Calculation: Cv(h) = 60. Q = 60 x 1.156 x 1 = 69.36 m3/h.

Lesson:

Frequently asked questions

Can I convert opening % to flow %?

Only with the manufacturer Cv(h) table or rangeability R. Otherwise the result is a guess.

Linear or equal-percentage?

Equal-percentage passes less than linear at the same mid opening; the exact ratio needs R.

Why is control poor below 10% open?

Most trims hunt and cavitate near the seat. Resize or use a smaller trim.

Sources and further verification

  1. Control valve Wikipedia
  2. Flow coefficient Wikipedia