What this calculator does
This estimator maps one controller output to two split-range valve commands around an adjustable split point. Below the split, Valve A is scaled from 0 to 100%; above the split, Valve B is scaled from 0 to 100%. Each position is clamped to the 0–100% range.

For output u and split s:
A = clamp(100u/s)
B = clamp(100(u−s)/(100−s))
Each 0–100% position is also converted to a linear 4–20 mA signal.
Reading the result
At u = 60% and s = 50%, Valve A reaches 100% and Valve B is 20%. Their signals are 20.00 mA and 7.20 mA. At u = 30%, Valve A is 60% (13.60 mA) and Valve B is clamped at 0% (4.00 mA).
The split point changes the handover location. It does not create overlap, deadband, characterization, fail action, or travel calibration. Values outside the active segment are clamped, so a valve remains fully open or closed while the other valve takes control.
When to use / when not to use
Use this screen to check arithmetic for a two-valve split-range command with linear 4–20 mA mapping. It does not size valves, select an overlap or deadband, account for actuator fail positions, characterize installed flow, or verify controller wiring and output limits. Confirm the actual sequence and handover behavior with the control-system configuration and a stroke test.
Input and output variables
- Split
- Valve A 0-50%, B 50-100%
- Overlap
- Deadband at midscale
- Sequence
- Which valve moves first
Worked example
At controller output 60% and split point 50%, Valve A is 100% / 20.00 mA and Valve B is 20% / 7.20 mA.
Standards: Ziegler-Nichols (starting point)
Frequently asked questions
How do I use the Split-Range Estimator?
Enter entered inputs with units as labeled, read each output with its substituted formula, then verify against datasheets and field readings before acting.
Is this result final?
Starting-point tuning only. Validate on the live loop before commissioning.
Learn
How to interpret the result
Check split-range valve positions.
Checklist before you rely on it
- Confirm units match the input labels before trusting the result.
Related calculators
Control Loops
First-Order Response (tau)
First-order 98% at 4 tau plus dead time.
Open calculatorControl Loops
Flow Signal Damping
Lag filter settle ~5x filter constant. Smaller alpha = heavier damping.
Open calculatorControl Loops
PID Form Converter
Parallel PID: Ki = Kp/Ti, Kd = Kp Td.
Open calculatorControl Loops
PID Tuning (Ziegler-Nichols)
Classic ZN P/PI/PID gains from Ku and Tu.
Open calculatorWorkspace
Save this calculation to your workspace
Save this calculation to your private workspace: keep inputs + result, compare scenarios side by side, and export a report with substituted formulas.
- Save projects — return to inputs, result, and report.
- Compare scenarios — see which option holds margin.
- Export report — PDF/CSV with formulas shown.
Sign in or create an account to save this calculation.